| FWC06B5FV1B | FWC07B5FV1B | FWC08B5FV1B | FWC09B5FV1B | |||||
|---|---|---|---|---|---|---|---|---|
| Geluidsdrukniveau op 1 m | Laag | dB(A) | 21.0 | 22.0 | 24.0 | 28.0 | ||
| Hoog | dB(A) | 29.0 | 33.0 | 39.0 | 43.0 | |||
| Standaard-accessoires | Montage- en bedieningshandleiding | 1 | 1 | 1 | 1 | |||
| Montagehandleiding | 1 | 1 | 1 | 1 | ||||
| Afvoerslang | 1 | 1 | 1 | 1 | ||||
| Metalen klem voor afvoerslang | 1 | 1 | 1 | 1 | ||||
| Sluitring voor ophangbeugel | 8 | 8 | 8 | 8 | ||||
| Schroeven | 4 | 4 | 4 | 4 | ||||
| O-Ring | 4 | 4 | 4 | 4 | ||||
| Isolatie | 6 | 6 | 6 | 6 | ||||
| Totaal geluidsniveau | Laag | dB(A) | 33.0 | 36.0 | 36.0 | 40.0 | ||
| Hoog | dB(A) | 43.0 | 47.0 | 53.0 | 57.0 | |||
| Waterdebiet | Waterdrukverlies | Verwarming | Hoog | kPa | 18 | 22 | 30 | 38 |
| Koeling | Hoog | kPa | 15 | 18 | 23 | 30 | ||
| Koelleidingmaten | Afvoer | mm | VP25 (buitendiam. 32, binnendiam. 25) | VP25 (buitendiam. 32, binnendiam. 25) | VP25 (buitendiam. 32, binnendiam. 25) | VP25 (buitendiam. 32, binnendiam. 25) | ||
| Water | Intrede | 3/4" BSP (vrouwelijke schroefdraad) | 3/4" BSP (vrouwelijke schroefdraad) | 3/4" BSP (vrouwelijke schroefdraad) | 3/4" BSP (vrouwelijke schroefdraad) | |||
| Uittrede | 3/4" BSP (vrouwelijke schroefdraad) | 3/4" BSP (vrouwelijke schroefdraad) | 3/4" BSP (vrouwelijke schroefdraad) | 3/4" BSP (vrouwelijke schroefdraad) | ||||
| Opgenomen vermogen | Hoog | kW | 0.046 | 0.055 | 0.077 | 0.107 | ||
| Laag | kW | 0.035 | 0.038 | 0.040 | 0.046 | |||
| Toegestane watertemperatuur | Verwarming | Max. | °C | 70 (4) | 70 (4) | 70 (4) | 70 (4) | |
| Min. | °C | 5 (4) | 5 (4) | 5 (4) | 5 (4) | |||
| Koeling | Min. | °C | 5 (4) | 5 (4) | 5 (4) | 5 (4) | ||
| Max. | °C | 70 (4) | 70 (4) | 70 (4) | 70 (4) | |||
| Afmetingen | Unit | Breedte | mm | 840 | 840 | 840 | 840 | |
| Diepte | mm | 840 | 840 | 840 | 840 | |||
| Hoogte | mm | 288 | 288 | 288 | 288 | |||
| Gewicht | Unit | kg | 29 | 29 | 29 | 29 | ||
| Ventilator | Luchthoeveelheid | Laag | m³/u | 708 | 804 | 852 | 1,014 | |
| Hoog | m³/u | 1,032 | 1,200 | 1,476 | 1,746 | |||
| Koelvermogen (standaardomstandigheden) | Totaal vermogen 4-pijps | Laag | kW | 4.3 (1) | 4.6 (1) | 4.8 (1) | 5.7 (1) | |
| Hoog | kW | 5.9 (1) | 6.3 (1) | 7.2 (1) | 8.3 (1) | |||
| Voelbaar vermogen 4-pijps | Laag | kW | 3.1 (1) | 3.3 (1) | 3.5 (1) | 4.0 (1) | ||
| Hoog | kW | 4.2 (1) | 4.6 (1) | 5.4 (1) | 6.4 (1) | |||
| Verwarmingsvermogen (standaardomstandigheden) | Vermogen 4-pijps | Laag | kW | 5.2 (3) | 5.5 (3) | 5.8 (3) | 6.8 (3) | |
| Hoog | kW | 6.9 (3) | 7.8 (3) | 9.2 (3) | 10.4 (3) | |||
| Power supply | Fase | 1~ | 1~ | 1~ | 1~ | |||
| Frequentie | Hz | 50 | 50 | 50 | 50 | |||
| Spanning | V | 220-240 | 220-240 | 220-240 | 220-240 | |||
| Opmerkingen | (1) - Koelen: lucht 27°CDB, 19°CWB; waterintrede 7℃; wateruittrede 12℃ | (1) - Koelen: lucht 27°CDB, 19°CWB; waterintrede 7℃; wateruittrede 12℃ | (1) - Koelen: lucht 27°CDB, 19°CWB; waterintrede 7℃; wateruittrede 12℃ | (1) - Koelen: lucht 27°CDB, 19°CWB; waterintrede 7℃; wateruittrede 12℃ | ||||
| (2) - Verwarming: 2-pijps: 20°C DB, 15°C NB; waterintrede 45°C; waterintrede 40°C; | (2) - Verwarming: 2-pijps: 20°C DB, 15°C NB; waterintrede 45°C; waterintrede 40°C; | (2) - Verwarming: 2-pijps: 20°C DB, 15°C NB; waterintrede 45°C; waterintrede 40°C; | (2) - Verwarming: 2-pijps: 20°C DB, 15°C NB; waterintrede 45°C; waterintrede 40°C; | |||||
| (3) - Verwarming: 4-pijps: 20°C DB, 15°C NB; waterintrede 65°C; waterintrede 55°C; | (3) - Verwarming: 4-pijps: 20°C DB, 15°C NB; waterintrede 65°C; waterintrede 55°C; | (3) - Verwarming: 4-pijps: 20°C DB, 15°C NB; waterintrede 65°C; waterintrede 55°C; | (3) - Verwarming: 4-pijps: 20°C DB, 15°C NB; waterintrede 65°C; waterintrede 55°C; | |||||
| (4) - Voer geen water van minder dan 5°C of meer dan 50°/70°C toe naar de unit, om beschadiging van de unit te voorkomen | (4) - Voer geen water van minder dan 5°C of meer dan 50°/70°C toe naar de unit, om beschadiging van de unit te voorkomen | (4) - Voer geen water van minder dan 5°C of meer dan 50°/70°C toe naar de unit, om beschadiging van de unit te voorkomen | (4) - Voer geen water van minder dan 5°C of meer dan 50°/70°C toe naar de unit, om beschadiging van de unit te voorkomen | |||||