Tabel met technische gegevens voor ERA-AY

ERA100A7Y1B ERA125A7Y1B ERA140A7Y1B
Koelvermogen Nom. 35°CDB kW 12.1 (1) 14 15.5 (1)
Verwarmingsvermogen Nom. 6°CNB kW 12.1 (2) 14 15.5 (2)
SEER 7.9 (3) 7.4 (3) 7.3 (3)
SCOP 4.9 (3) 4.5 (3) 4.5 (3)
Capaciteitsindex Min.   63 100 100
  Max.   100 125 140
Afmetingen Unit Hoogte mm 869 869 869
    Breedte mm 1100 1100 1100
    Diepte mm 460 460 460
Gewicht Unit kg 102 102 102
Ventilator Externe statische druk Max. Pa 45 45 45
Compressor Type   Hermetisch gesloten swingcompressor Hermetisch gesloten swingcompressor Hermetisch gesloten swingcompressor
Bedrijfsbereik Koelen Min. °CDB -5 -5 -5
    Max. °CDB 46 46 46
Werkingsbereik Verwarmen Min. °CWB -20 -20 -20
    Max. °CWB 15.5 15.5 15.5
Geluidsvermogenniveau Koelen Geluidsvermogenniveau-=-Koelen-=-Nom.-=-dB(A) dB(A) 67 68.1 (4) 69
Geluidsdrukniveau op 1 m Koelen Nom. dB(A) 49 51 51
Koelmiddel Type   R-32 R-32 R-32
  GWP   675 675 675
Koudemiddel Vulling tCO2Eq 2.3 2.3 2.3
Koelmiddel Vulling kg 3.4 3.4 3.4
Leidingaansluitingen Vloeistof Type   Hardsoldeerverbinding Hardsoldeerverbinding Hardsoldeerverbinding
    Buitendiameter mm 9.52 9.52 9.52
  Gas Type   Hardsoldeerverbinding Hardsoldeerverbinding Hardsoldeerverbinding
    Buitendiameter mm 15.9 15.9 15.9
Koelleidingmaten Totale leidinglengte Systeem Werkelijk m 50 (6) 50 (6) 50 (6)
  Hoogteverschil OU - IU Buitendeel op de hoogste positie m 50 50 50
      Binnendeel op de hoogste positie m 40 40 40
Standaard-accessoires Auxiliary piping set 1 1 1
  Installation and operation manual 1 1 1
Voeding Naam   Y1 Y1 Y1
  Fase   3N~ 3N~ 3N~
Spanningsvorm Frequentie Hz 50 50 50
  Spanning V 380-415 380-415 380-415
Opmerkingen (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  (3) - Gedefinieerd voor een systeemcapaciteitsverhouding van 100% ± 5%, geconfigureerd voor volledige luchthercirculatietoepassingen. (3) - Gedefinieerd voor een systeemcapaciteitsverhouding van 100% ± 5%, geconfigureerd voor volledige luchthercirculatietoepassingen. (3) - Gedefinieerd voor een systeemcapaciteitsverhouding van 100% ± 5%, geconfigureerd voor volledige luchthercirculatietoepassingen.
  (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates. (4) - Sound power level is an absolute value that a sound source generates.
  (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
  (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual (6) - Refer to refrigerant pipe selection or installation manual
  (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
  (8) - MSC is de maximale stroom tijdens de aanloop van de compressor. Deze unit gebruikt alleen invertercompressors. De opstartstroom is altijd ≤ max. bedrijfsstroom. (8) - MSC is de maximale stroom tijdens de aanloop van de compressor. Deze unit gebruikt alleen invertercompressors. De opstartstroom is altijd ≤ max. bedrijfsstroom. (8) - MSC is de maximale stroom tijdens de aanloop van de compressor. Deze unit gebruikt alleen invertercompressors. De opstartstroom is altijd ≤ max. bedrijfsstroom.
  (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. (9) - MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
  (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (10) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
  (11) - TOCA means the total value of each OC set. (11) - TOCA means the total value of each OC set. (11) - TOCA means the total value of each OC set.
  (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan (12) - FLA means the nominal running current of the fan
  (13) - Raadpleeg het boek met technische gegevens of de installatiehandleiding voor de volumebeperkingen van de AHU HEX. (13) - Raadpleeg het boek met technische gegevens of de installatiehandleiding voor de volumebeperkingen van de AHU HEX. (13) - Raadpleeg het boek met technische gegevens of de installatiehandleiding voor de volumebeperkingen van de AHU HEX.
  (14) - Meer details over standaardaccessoires vindt u in de installatie-/gebruikshandleiding. (14) - Meer details over standaardaccessoires vindt u in de installatie-/gebruikshandleiding. (14) - Meer details over standaardaccessoires vindt u in de installatie-/gebruikshandleiding.